Plumbing Systems
Plumbing is a system of piping, apparatus, and fixtures for water
distribution and waste disposal within a building. This chapter covers
the basic water supply and water distribution systems, the theater of
operations (TO) water supply and water distribution systems, and the
sewerage system. Plumbing also includes the installation and maintenance
of these systems. When architects design a building, they prepare a set
of prints and a set of specification sheets detailing the types and
quality of materials to be used. Plumbers use the prints and
specifications to layout and plan the project.
1-1. A water supply system receives, treats, and moves water to a
water distribution system. Water may come from a stream or lake, a deep
or shallow well, or a reservoir which collects surface water. The water
supply system purifies and pumps the water into a storage tank. After
the water is purified, it is released into the distribution system. The
distribution system is an arrangement of connected pipes (called a run)
that carries the water to its destination. This system usually has a
means of heating some of this water.Basic Water Supply And Water Distribution Systems
PLANS
1-2. See Appendix B for information on construction plans, prints, drawings, and plumbing and heating symbols.
WATER SUPPLY AND WATER DISTRIBUTION PLANS
1-3. A plumber should be able to install a complete water supply
system by using a plan together with standard and special detail
drawings and a BOM. A standard detail drawing will show the water heater
and standard storage tank connections. The plan will show the type of
piping by size and fittings (see Appendix B).
UTILITY- AND BUILDING-WASTE SYSTEM PLANS
1-4. For more information on utility- and building-waste system plans, see Appendix B.
UNIT-CONSTRUCTION AND PACKAGE-UNIT PRINTS
1-5. Prints are used for structures and equipment in water supply
and water distribution systems. The type of print depends on whether
the unit is constructed or if it is a package unit to be assembled in
the field (see Appendix B, paragraph B-8).
BOM
1-6. The designer (architect) or draftsman usually prepares a BOM
(DA Form 2702) when preparing the original drawings. However, if no BOM
accompanies the field prints, the plumber must compile it. Appendix C
gives instructions for preparing a BOM.
WATER SUPPLY LINES AND BRANCHES
1-7. The main water supply system provides potable cold water at
the main at a pressure that meets National Plumbing Code standards. The
water service main for the plumbing installation Ts into the main water
supply. The plumbing system must provide enough water for normal use at
each outlet.
1-8. Fixture supply risers take water from the main supply to the
fixtures on each floor level. Each fixture supply riser must have a
diameter large enough to supply water to all the fixtures it connects.
The size is determined by the design load for the riser (refer to
Appendix D, Tables D-3 or D-4).
PIPE SELECTION
1-9. Cold-water systems may use galvanized-iron or
galvanized-steel pipe, copper tubing, plastic pipe, brass, cast iron,
galvanized, wrought iron, or other approved material. The material used
depends on the—
• Amount of water to be supplied.
• Water pressure.
• Corrosion factor for different types of pipe in different temperatures.
• Cost.
• Availability.
PIPE SIZE
1-10. The size of water supply piping depends on the—
• Water pressure and friction loss through the length of the pipe.
• Number and kinds of fixtures installed (fixture demand).
• Number of fixtures in use at a given time (factor of simultaneous use).
• Type of flushing devices (refer to Chapter 4).
Friction Loss
1-11. When a liquid flows through a pipe, layers move at
different speeds, with the center layer moving fastest. This resistance
to flow (called friction loss) varies with different types of pipe. Pipe
friction, in turn, causes a drop in water pressure. In a small pipe,
this friction loss is overcome by increasing the water pressure. If
higher water pressure is not possible, increasing the pipe size can
reduce friction loss. See Appendix D for friction loss in different
types of pipe.
Water Hammer
1-12. In a water supply system, water hammer occurs when flowing
water is stopped abruptly or cannot be compressed, causing the flowing
water to slam against the valve with the same amount of pressure as
applied to the water system (such as when you flush a water closet, the
water closet's tank completes the filling action, and the control valve
in the tank closes).
1-13. The effects of water hammer are noise from rattling pipes
and sometimes leaky pipe joints, both of which can be eliminated easily
by installing a device called a expansion chamber to slow the water in
the plumbing system. The expansion chamber shown in Figure 1-1 is capped
at the upper end causing it to fill with air, not water. Air, unlike
water, can be compressed. Therefore, when the water flow is stopped
abruptly, the air in the air chamber works like an automotive shock
absorber relieving the slamming action against the valve. Install
expansion chambers in the water supply system on both hot and cold
service lines at each major fixture within a structure.
1-14. Expansion chambers can be purchased or fabricated. Figure
1-1 shows an example of a constructed expansion chamber. The type of
pipe and the dimensions used are not critical, but ensure that the
section identified as the riser is at least 6 inches long.
Figure 1-1. Expansion Chamber Construction
Water Pressure
1-15. Pressure in the main usually ranges from 45 to 60 pounds
per square inch (psi). If the pressure is over 60 psi, a
pressure-reducing valve must be placed in the water service line at its
entry to the building. The size of the water service pipeline, the rate
of use, the length of the line, and the outlet height in the system
control the pressure available at the outlet. If the water pressure is
less than 15 psi, use a tank and a pump or other means to provide
pressure. If the water pressure is over 80 psi, use an approved pressure
regulator.
Calculations for Sizing Pipe
1-16. The minimum practical size for a water service line is 3/4
inch. This size should be used even when calculations indicate a smaller
one. Calculations for factoring loss of pressure in complex systems are
beyond the range of this manual. For simple systems, use approximate
figures to find the pipe size. Tables D-1 and D-2, Appendix D, give
capacities and psi for galvanized-steel/iron pipe, copper tubing, and
plastic pipe. Use these tables combined with the maximum fixture demand
and simultaneous use factor to determine pipe sizes.
1-17. Maximum Fixture Demand. The maximum fixture demand in
gallons per minute (GPM) is the total amount of water needed to supply
all the fixtures at the same time. Estimate the maximum fixture demand
by counting the number and types of fixtures in the plumbing system.
Table 1-1 gives the maximum fixture demand for different fixtures.
1-18. For example, what is the maximum fixture demand for a
plumbing system which consists of the following 14 fixtures: 2 water
closets, 4 lavatories, 2 showers, 3 urinals, 1 slop sink, 1 laundry tub,
and 1 floor drain?
Use Table 1-1 and the following steps:
Step 1. Multiply the number of each fixture by the GPM of that type fixture (from Table 1-1).
Step 2. Total these figures.
1-19. The result is a maximum fixture demand of 313.5 GPM.
NOTE: Use the fixture demand (313.5 GPM) with the simultaneous use factor to select the pipe size.
1-20. Simultaneous-Use Factor. The simultaneous-use factor is the
percentage of fixtures potentially in use at a given time (Table 1-2).
It is an estimate of the total demand on a water supply system,
expressed as water supply fixture units. Simultaneous-use factors
decrease as the number of fixtures in a building increases. Use the
formulas in Table 1-2 to determine simultaneous use factor.
1-21. If a table for the simultaneous-use factor is not
available, estimate the probable demand by computing 30 percent of the
maximum fixture demand in gallons.
1-22. Continuing the example in paragraph 1-18, the 14 fixtures
would have a simultaneous use of 42.72 percent (round up to 43 percent).
Since the fixture demand was 313.5 GPM, the water service line must
have a capacity of 43 percent of 313.5 (110 GPM). What size of pipe
would be needed for a 60-foot long pipeline with a pressure at the main
of 45 psi (refer to Appendix D, Tables D-1 and D-2)?
Step 1. Read down the 60-foot column in Tables D-1 or D-2, to 1 1/2 inch diameter.
Step 2. Read across (left) to the psi column and establish the given as 45 psi.
Step 3. Read back to the 60-foot column. TableD-1 shows 150GPM(the quantity that includes 110 GPM);
Table D-2 shows 155 GPM(round up to 160 GPM).
1-23. Either 1 1/2-inch galvanized, copper, or plastic piping would be large enough for the water service line.
NOTE: Remember, the minimum practical size for a water service
line is 3/4 inch. This size should be used even when calculations
indicate a smaller size.
INSTALLATION
Main Water Supply Line
1-24. The main water supply is a pipe, usually hung from a
ceiling, with branches connected to serve the fixture risers. This
supply pipe has the same diameter as the water service from the main and
is centrally located to provide short takeoffs to the fixture supply
risers throughout the building. To reduce friction loss, lay the main
supply piping as straight as possible. The main supply pipe must not sag
or trap water. It should be graded slightly, up to 1/4 inch per foot,
dropping toward the water meter. At the low end of the
grade, place a drip cock or stop-and-waste valve for draining the pipe in the winter. A drainpipe may be needed to carry the wastewater from the opening in the valve to a floor drain or sump. If it is impossible to grade all the piping to one point, all parts that cannot be centrally drained should have separate drip cocks or stop-and-waste valves. The main supply pipe must be well supported to take its weight off the fittings and to prevent leaks.
grade, place a drip cock or stop-and-waste valve for draining the pipe in the winter. A drainpipe may be needed to carry the wastewater from the opening in the valve to a floor drain or sump. If it is impossible to grade all the piping to one point, all parts that cannot be centrally drained should have separate drip cocks or stop-and-waste valves. The main supply pipe must be well supported to take its weight off the fittings and to prevent leaks.
Fixture Supply Risers
1-25. Use reducing Ts to connect fixture supply risers to the
main supply. Run the risers through the interior walls of the building.
Tighten all the joints before the partitions are finished. Use pipe
rests or clamps to support vertical fixture supply risers at each floor
level. (Fixture supply risers must not depend on the horizontal branches
for support.) Horizontal-fixture branches should be well supported and
graded upward toward the vertical-fixture supply risers.
Valves
1-26. Install gate valves in each vertical supply riser, so that a
section can be repaired without shutting off the water to other
sections. Small gate valves on the supply to each fixture allows for
shutting off the water for faucet repairs.
TESTING FOR LEAKS
1-27. Inspecting for leaks is important. A leaky joint wastes
water and causes costly damage to the building. In new construction,
test the entire system for leaks before the floor and partitions are
closed up. When performing this test, use the water pressure from the
main that feeds the system. While the system is under pressure, inspect
each joint for moisture. If a leak is detected in a joint, tighten the
joint or replace it by cutting the pipe and connecting a new section
with a union. When working with copper soldered joints or plastic
solvent-cement joints, drain the pipe and then connect the joint. Copper
compression joints can be tightened or replaced.
DISINFECTING THE PIPING SYSTEM
1-28. After installation or repair, clean and disinfect plumbing
pipes and other parts of a water supply system carrying drinking water
before use. Flush the system to remove dirt, waste, and surface water.
Disinfect each unit with a chemical such as a solution of hypochlorite
or chlorine.
Dosage
1-29. Under average conditions, use the dosages (in parts per
million [ppm]) in Table 1-3. The chlorine dosage required to disinfect a
unit depends on the—
• Contact time.
• Amount of organic chlorine-consuming material present.
• Volume of water to be disinfected. Table 1-4 gives the volume of water for different sizes and lengths of pipe.
Application
1-30. Use portable gas chlorinators to apply the liquid chlorine.
Chlorine cylinders should not be connected directly to the mains
because water may enter the cylinder and cause severe corrosion,
resulting in dangerous leakage.
A solution of hypochlorite is usually applied by measuring pumps,
gravity feed mechanisms, or portable pipe-disinfecting units. Use the
following steps to apply disinfectant:
Step 1. Flush all sections thoroughly at a velocity of at least 3 feet per second (fps) until all the dirt and mud are removed.
Step 2. Plug all branches and other openings with plugs or heads properly braced to prevent blowouts.
Step 3. Insert the disinfectant into the mains through taps or hydrants at the ends of each section.
Step 4. Bleed out any air trapped in the line.
Step 5. Add the predetermined chlorine dosage as the main slowly fills with water.
Step 6. Continue feeding until the water coming from the supply end contains the desired amount of chlorine.
Step 7. Keep the chlorinated water in the unit for 24 to 48 hours.
Step 8. Flush the main until the water contains only the amount of chlorine normally in the supply.
Step 9. Analyze samples daily for bacteria until the analyses
show no further need for disinfection. If the samples are
unsatisfactory, rechlorinate.
MAINTENANCE AND REPAIR
Corrosion
1-31. Galvanic corrosion (resulting from a direct current of
electricity) occurs in a plumbing system that includes two different
kinds of metal pipe, such as galvanized pipe and copper pipe. See
Chapter 3 for reducing and repairing corrosion.
Scale
1-32. Hard water contains a large amount of calcium and magnesium
compounds, which prevent soap from lathering. This forms a scum that
slows the flow of water. The scum deposits harden and form scale. See
Chapter 3 for reducing and removing scale.
Frozen Pipes
1-33. Water supply lines may freeze when exposed to temperatures
below 32 degrees Fahrenheit. Outside pipes must be buried below the
frost line. In northern zones, this is 4 feet or more. If the building
temperature falls below freezing, inside pipes may also freeze, causing
the pipe to break at the weakest point. Use the procedures in Chapter 3
to thaw frozen pipes.
TAPPING THE WATER MAIN
1-34. Water mains are usually cast iron, 8 inches or more in
diameter. If the main is less than 8 inches in diameter, taps should be 2
inches or smaller. Use Figure 1-2 and the following steps to tap the
water main:
Step 1. Dig to expose the pipe at the point where the tap is to be made. Dig as close to the top of the water main as possible.
Step 2. Clean all dirt and rust off the pipe at that point.
Step 3. Place the gasket of the water-main self-tapping machine on the pipe, and set the saddle of the machine on the gasket.
Step 4. Wrap the chain around the pipe, and tighten it to clamp the water main self-tapping machine to the pipe.
Step 5. Remove the cap from the cylinder of the machine, and place the combination drill and tap in the boring bar.
Figure 1-2. Tapping the Water Main
Step 6. Reassemble the machine by putting the boring bar through the cylinder and tightening the cap.
Step 7. Open the flap valve between the compartments.
Step 8. Start drilling the hole by applying pressure at the feed yoke and turning the ratchet handle until the drill enters the main.
Step 9. When the tap starts threading the hole, back off the feed yoke to prevent stripping the threads.
Step 10. Continue to turn the boring bar until the ratchet handle can no longer be turned without extra force.
Step 11. Remove the tap from the hole by reversing the ratchet. Then, back the boring bar out by turning it counterclockwise.
Step 12. Close the flap valve between the upper and lower compartments.
Step 13. Drain the water from the cylinder through the bypass.
Step 14. Remove the cap and drill tool. Place a corporation stop
(Figure 1-3, page 1-10) in the boring bar, ensuring that the stop is
closed.
Step 15. Repeat steps 6 and 7.
Step 16. Turn the ratchet handle to thread the corporation stop into the pipe.
Step 17. Repeat step 13.
Step 18. Remove the cap from the cylinder, and unbolt the boring bar from the corporation stop.
Step 19. Remove the lower chamber from the pipe.
Step 20. Inspect for leaks.
Step 21. If the corporation stop leaks, tighten it with a suitable wrench.
INSTALLING CURB AND METER STOPS
1-35. Curb and meter stops control the water entering the building. Figure 1-3 shows this installation.
Figure 1-3. Curb and Meter Stops
CURB STOP
1-36. After tapping the water main and inserting the corporation
stop, install the curb stop in a suitable position. It is usually set in
a cast-iron stop box to provide easy access in the water service
between the curb and the building.
1-37. The stop box has a variable telescopic length for use on
different grades. When the water service is copper, join the curb stop
to the service piping with a compression joint. After installing the
curb stop, run the water service line to the building and through the
building wall to the inside of the basement. The water service line can
be laid in the same trench as the sewer. The bottom of the water pipe at
all points should be at least 12 inches above the top of the sewer
line. The water pipe should be placed on a solid shelf excavated at one
side of the common trench with a minimum clear horizontal distance of at
least 12 inches from the sewer line. It must be placed in the ground at
a level deeper than the maximum depth of frost penetration.
METER AND METER STOP
1-38. After running the water service lines through the side of
the building and closing the holes around the service pipe with
waterproof cement, install the water meter and meter stop.
Meter Stop
1-39. The meter stop is a ground-joint valve, which controls and
shuts off the flow of water into the building. Place the meter stop as
close to the service pipe entry as possible.
Water Meter
1-40. The water meter, installed near the meter stop, measures the amount of water used in the building.
1-41. Often the meter and stop are placed in a meter vault that
replaces the stop box at the curb. In this case, place a stop-and-waste
valve in the line where the water service enters the building.
HOT-WATER SUPPLY SYSTEM
1-42. The hot-water system consists of a water heater and a
piping system. This system runs parallel to the cold-water pipes running
to the plumbing fixtures (faucets) where hot water is desired. A
standard detail drawing will show the water heater and standard
storage-tank connections. The water heater is fueled by gas, oil,
electricity, or possibly solar energy.
WATER HEATERS
1-43. Water heaters are classified into four categories:
range-boiler, gas, oil burning, and electric. See Chapter 5 for water
heaters.
PIPE SELECTION
1-44. The pipes used in hot-water systems are similar to those
used in cold water supply systems. Old hot-water systems used
wrought-iron or steel pipe. Newer systems use chlorinated polyvinyl
chloride (CPVC) plastic pipe, since CPVC resists corrosion. Copper is
the most commonly used piping for distribution.
PIPE SIZE
1-45. To size the hot-water main supply lines and the risers, follow the same procedure as for basic water supply.
INSTALLATION
1-46. Installation begins with a water-heating device and the
main supply line from that device. Grade the hot-water supply to a
centrally located drip cock near the water heater. Water for the
fixtures at various levels throughout the building is taken from the
main hot-water supply by fixture supply risers. Each of the risers
should have a valve.
ONE-PIPE SYSTEM
1-47. Buildings with a large floor area or with several floors
need the supply of hot water to the fixture as soon as possible after
the tap is opened. In a one pipe system, such as that used for
cold-water supply, a lag occurs from the time the hot-water tap is
opened until the water travels from the water heating device to the tap.
TWO-PIPE SYSTEM
1-48. To overcome this time lag, use a two-pipe,
circulating-water supply system (Figure 1-4). Hot water passes from the
water heater through the main fixture supply risers and returns through a
line to the water heater. This looped system circulates the hot water
at all times. Warm water tends to rise and cold water tends to fall,
creating circulation. The water within the loop is kept at a high
temperature. When a tap is opened, hot water flows from the hot-water
supply riser into the branch and out of the tap. The cold-water filler
within the hot-water storage tank (water heater) has a siphon hole near
the top of the tank. If reduced pressure occurs at point A, the siphon
hole allows air to enter the cold-water filler. This breaks the vacuum
and prevents back siphonage of hot water into the cold-water
distribution system.
1-50. This circulating supply system (Figure 1-4) is an
overhead-feed and gravity-return system and is likely to become
air-locked. An air lock prevents circulation of the hot water. Since air
collects at the highest point (B) of the distribution piping, the most
practical way to relieve the air lock is to connect an uncirculated
riser to the line at that point. The air lock is relieved when a fixture
on the uncirculated riser is used.
MAINTENANCE AND REPAIR
1-51. Maintenance and repair of hot-water systems is similar to what was previously discussed.
FIRE-PROTECTION WATER SYSTEMS
FIRE HYDRANTS
1-52. Fire protection for buildings of fire-resistant
construction is provided by fire hydrants. These are usually located at
least 50 feet from each building or from the water distribution system
within the building.
Figure 1-4. Circulating Hot-Water System (Two-Pipe)
AUTOMATIC SPRINKLER SYSTEMS
1-53. Automatic sprinkler systems are used for fire-resistant
structures only when the value, the importance of the contents or
activity, or the possibility of a fire hazard justifies a sprinkler
system. Buildings of frame and ordinary construction that are more than
two stories high and house tops will be protected by automatic sprinkler
systems.
THEATER OF OPERATIONS WATER SUPPLY AND DISTRIBUTION SYSTEM
1-54. In a TO, there is always a chance the Army may have to take
over the repair and operation of a municipal water system. Although
most systems will be similar to those used in the US, problems can be
expected in obtaining replacement parts and operating supplies. Sizes
and dimensions of basic components can be expected to differ from those
in the US and even require the use of metric tools. Also, certain
nations may use different disinfecting methods than chlorine. Under
these circumstances, the Army should consider hiring former local
employees who are familiar with the equipment to operate and maintain
the system.
WATER DISTRIBUTION METHODS
1-55. After water is purified, it is released into the
distribution system. The distribution of large quantities of water under
tactical conditions will be by pipelines, trucks carrying bladders, and
5,000-gallon tanker trucks. Small quantities can be picked up from tank
farms or storage and distribution points in 400-gallon water trailers
or in refillable drums, 5-gallon cans, and individual containers.
PLANS AND INSTALLATION
1-56. Appendix B, Figure B-1, shows a water distribution system
plan for a hospital area. The general location and size of the pipes are
shown, together with the valves, sumps, water tank, and other fixtures.
Generally, the symbols used on distribution-system plans are the same
as those for water plumbing. (See Appendix B, Section II, for standard
plumbing symbols.) The plumber who installs the system determines the
location of the pipes and other equipment to suit the climate and
terrain, and according to the National
Plumbing Codes.
Plumbing Codes.
Plumbing system supplies water and helps manage waste, it is essential that a house has an efficient one. Repairing any plumbing problems important because of how home relies on the plumbing system for its water supply.
ReplyDeleteThanks for your sharing
ReplyDeleteVery Very nice and fully interesting article. I am impressed with your post. Thanks for sharing wonderful post with us. It is really helping information.
ReplyDeleteWe are from Plumb Right Plumbing Services offer best and cheap services in texas, visit us Plumbing Supply Houston
thanks for your comment
ReplyDeleteAlways Try to compare these copper plumbing parts items before you decide to buy ones for fixing and or upgrading your plumbing system at house.
ReplyDeleteWe are from Plumb Right Plumbing Services offer best and cheap services in Texas, visit us Cheap Plumbing Services Houston
CPVC pipes are really great the best options for the storing of hot water and cold water. These pipes are not corroded by chemicals as well and thus they can be used as the pipes for drinking water.
ReplyDeleteCPVC Fittings Manufacturer, CPVC Pipes & Fittings, CPVC Pipes manufacturers
Nice & great work information, which you have mentioned in your post. I really appreciate and like you work.
ReplyDeletePlumbers houston
Good article with useful information. Check out Plumbing Materials Online
ReplyDeleteGreat information, Thanks for sharing.
ReplyDeletePlumbing Pipe
Start the machine again and let it stay ready. Leesburg VA
ReplyDeleteThe reason that you need to make sure that your plumber is licensed is to ascertain that he will adhere to the strict codes set by the local government. He will be legally obligated to provide you with work of a certain standard. Columbus plumber
ReplyDeleteAlways check that you are working with a licensed plumber, ask to see his state license! Licensed plumbers have the work experience, training, and are familiar with current state and local plumbing codes. reno 24 hour plumber
ReplyDelete